System design of the control of a 8

System design of the control of a 8 elevators x 40 floor building
1. System diagram
- To access 40 floors, it needs 40 relays. So, 3 units of EXP-2016 provides 48 relay output control
- It also needs a reader control board inside each elevator. 1 unit of EXP-2024
- EXP-1032 controls the EU (such as EXP-2016 and EXP-2024) by rs485. One set of EXP-1032 could
control maximum 32 modules through rs485 bus.
- Requirement of rs485 bus: shielded twisted pair cable (better reliability in data transmission),
travelling cable (flexible, not easily broken).
- EXP-1032 could communicate with computer through LAN/WAN.
- Total hardware required
- 8 elevators x (3 x EXP-2016 + EXP-2024 + 1 x reader)
EXP-2016 (elevator module) 24 units
EXP-2024 (reader/door module) 8 units
EXP-1032 (CPU module) 1 unit
Reader (e.g. AY-M12) 8 units
2. System diagram in more detail
3. Explanation in hardware connection, and how it work
Note: Due to limited space, only 2 EXP-2016 + 1 EXP-2024 are drawn in this diagram.
How it works
- The elevator control system is already provided by the elevator company. We do not intend to
change the circuit in the original control system.
- As shown in the diagram, the elevator broad relays just enable/disable the buttons in the elevator.
- When relay close, it enable the buttons
- When relay open, it disable the buttons
- So the users could only access to the floors which is allowed.
- The selection for which relays to be activated is programmable in the Expanse system. (See the
procedures I described in the next pages)
- The relays, across all modules, could be grouped into a number of output groups and elevator
groups.
- The users could be assigned to any of these groups.
- When the user grant access by using his cards/PIN, only the relays belonged to his group is activated,
and thus restricts the user to go to certain number of floors only.
4. System programming: Rename the output relay to Level 1 to Level 40
- Rename the output (of each relay) to Level-1 up to Level-40, to let us easier review in event logs,
and troubleshooting.
5. System programming: Create Output Groups and Elevator Groups to control relays
Output Groups
- As for example, two output groups and two elevator groups are created, such that
- OutputGrp1-LVL-1-10 control relays related to floor 1 to 10
- OutputGrp1-LVL-11-20 control relays related to floor 11 to 20
- In this example,
the prefix “OutputGrp1” means elevator #1.
“LVL-1-10” means this group could only access level 1 to level 10.
- If some of the relays are damaged after using for a number of years, we could assign the spare relays
(relays that are not used currently) to the group, saving the cost of module replacement.
Elevator Groups
- assigning reader(s) and output group to elevator group
6. Assigning elevator group to user
7. Run a test
- Two users and two cards are enrolled to the Expanse system, such that they could grant access by
presenting cards on readers.
- The user put his card on reader, and then presses one of the enabled button within 4 seconds.
- As shown in the above settings, user8647 is programmed to access only level 1-10. Therefore, in the
event log, only relays of 1 to 10 are activated.
- The duration for the relay activation is also programmable. By default, it is 4 seconds. It means if the
button is not pressed within 4 seconds, it is time out. The user needs to present card again.
0/5000
Dari: -
Ke: -
Hasil (Bahasa Indonesia) 1: [Salinan]
Disalin!
System design of the control of a 8 elevators x 40 floor building1. System diagram- To access 40 floors, it needs 40 relays. So, 3 units of EXP-2016 provides 48 relay output control- It also needs a reader control board inside each elevator. 1 unit of EXP-2024- EXP-1032 controls the EU (such as EXP-2016 and EXP-2024) by rs485. One set of EXP-1032 couldcontrol maximum 32 modules through rs485 bus.- Requirement of rs485 bus: shielded twisted pair cable (better reliability in data transmission),travelling cable (flexible, not easily broken).- EXP-1032 could communicate with computer through LAN/WAN.- Total hardware required- 8 elevators x (3 x EXP-2016 + EXP-2024 + 1 x reader)EXP-2016 (elevator module) 24 unitsEXP-2024 (reader/door module) 8 unitsEXP-1032 (CPU module) 1 unitReader (e.g. AY-M12) 8 units2. System diagram in more detail3. Explanation in hardware connection, and how it workNote: Due to limited space, only 2 EXP-2016 + 1 EXP-2024 are drawn in this diagram.How it works- The elevator control system is already provided by the elevator company. We do not intend tochange the circuit in the original control system.- As shown in the diagram, the elevator broad relays just enable/disable the buttons in the elevator.- When relay close, it enable the buttons- When relay open, it disable the buttons- So the users could only access to the floors which is allowed.- The selection for which relays to be activated is programmable in the Expanse system. (See theprocedures I described in the next pages)
- The relays, across all modules, could be grouped into a number of output groups and elevator
groups.
- The users could be assigned to any of these groups.
- When the user grant access by using his cards/PIN, only the relays belonged to his group is activated,
and thus restricts the user to go to certain number of floors only.
4. System programming: Rename the output relay to Level 1 to Level 40
- Rename the output (of each relay) to Level-1 up to Level-40, to let us easier review in event logs,
and troubleshooting.
5. System programming: Create Output Groups and Elevator Groups to control relays
Output Groups
- As for example, two output groups and two elevator groups are created, such that
- OutputGrp1-LVL-1-10 control relays related to floor 1 to 10
- OutputGrp1-LVL-11-20 control relays related to floor 11 to 20
- In this example,
the prefix “OutputGrp1” means elevator #1.
“LVL-1-10” means this group could only access level 1 to level 10.
- If some of the relays are damaged after using for a number of years, we could assign the spare relays
(relays that are not used currently) to the group, saving the cost of module replacement.
Elevator Groups
- assigning reader(s) and output group to elevator group
6. Assigning elevator group to user
7. Run a test
- Two users and two cards are enrolled to the Expanse system, such that they could grant access by
presenting cards on readers.
- The user put his card on reader, and then presses one of the enabled button within 4 seconds.
- As shown in the above settings, user8647 is programmed to access only level 1-10. Therefore, in the
event log, only relays of 1 to 10 are activated.
- The duration for the relay activation is also programmable. By default, it is 4 seconds. It means if the
button is not pressed within 4 seconds, it is time out. The user needs to present card again.
Sedang diterjemahkan, harap tunggu..
Hasil (Bahasa Indonesia) 2:[Salinan]
Disalin!
Desain sistem kontrol dari 8 elevator x 40 lantai bangunan
1. Diagram sistem
- Untuk mengakses 40 lantai, perlu 40 relay. Jadi, 3 unit EXP-2016 menyediakan 48 kontrol relay keluaran
- Ini juga membutuhkan panel kontrol pembaca dalam setiap lift. 1 unit EXP-2024
- EXP-1032 kontrol Uni Eropa (seperti EXP-2016 dan EXP-2024) dengan rs485. Satu set EXP-1032 bisa
mengontrol maksimum 32 modul melalui rs485 bus.
- Kebutuhan rs485 bus: terlindung kabel twisted pair (keandalan yang lebih baik dalam transmisi data),
bepergian kabel (fleksibel, tidak mudah pecah).
- EXP-1032 bisa berkomunikasi dengan komputer melalui LAN / WAN.
- Jumlah hardware yang dibutuhkan
- 8 elevator x (3 x EXP-2016 + EXP-2024 + 1 x reader)
EXP-2016 (lift modul) 24 unit
EXP-2024 (reader / modul pintu) 8 unit
EXP -1032 (modul CPU) 1 unit
Reader (misalnya AY-M12) 8 unit
2. Diagram sistem secara lebih rinci
3. Penjelasan sehubungan hardware, dan bagaimana cara kerjanya
Catatan: Karena keterbatasan tempat, hanya 2 EXP-2016 + 1 EXP-2024 diambil dalam diagram ini.
Cara kerjanya
- Sistem kontrol lift sudah disediakan oleh perusahaan lift. Kami tidak bermaksud untuk
mengubah sirkuit dalam sistem kontrol yang asli.
- Seperti yang ditunjukkan dalam diagram, relay luas lift hanya mengaktifkan / menonaktifkan tombol di lift.
- Ketika dekat relay, itu mengaktifkan tombol
- Ketika relay terbuka, itu menonaktifkan tombol
- Jadi pengguna hanya bisa akses ke lantai yang diperbolehkan.
- Pemilihan yang relay harus diaktifkan diprogram dalam sistem Hamparan. (Lihat
prosedur yang saya jelaskan di halaman berikutnya)
- The relay, di semua modul, dapat dikelompokkan menjadi beberapa kelompok output dan lift
kelompok.
- Para pengguna dapat ditugaskan untuk salah satu kelompok.
- Ketika pengguna akses hibah dengan menggunakan kartunya / PIN, hanya relay milik kelompoknya diaktifkan,
sehingga membatasi pengguna untuk pergi ke sejumlah lantai saja.
4. Pemrograman sistem: Ubah nama output relay ke Level 1 sampai Level 40
- Mengubah nama output (masing-masing relay) ke-Level 1 hingga Level-40, untuk memberitahu kami tinjauan lebih mudah dalam event log,
dan pemecahan masalah.
5. Pemrograman sistem: Buat Kelompok Output dan Elevator Grup untuk mengendalikan relay
Grup Keluaran
- Sebagai contoh, dua kelompok output dan dua kelompok lift diciptakan, sehingga
- relay OutputGrp1-LVL-1-10 pengendalian yang berhubungan dengan lantai 1 sampai 10
- OutputGrp1- relay LVL-11-20 pengendalian yang berhubungan dengan lantai 11-20
- Dalam contoh ini,
awalan "OutputGrp1" berarti lift # 1.
"LVL-1-10" berarti kelompok ini hanya bisa mengakses tingkat 1 ke tingkat 10.
- Jika beberapa dari relay rusak setelah menggunakan selama beberapa tahun, kita bisa menetapkan relay cadangan
(relay yang tidak digunakan saat ini) ke grup, menghemat biaya penggantian modul.
Elevator Grup
- menugaskan pembaca (s) dan kelompok output Kelompok lift
6. Menetapkan kelompok Lift ke pengguna
7. Menjalankan tes
- Dua pengguna dan dua kartu yang terdaftar pada sistem Hamparan, sehingga mereka bisa memberikan akses dengan
menghadirkan kartu pada pembaca.
- Pengguna menempatkan kartu namanya pada pembaca, dan kemudian menekan salah satu tombol diaktifkan dalam waktu 4 detik.
- Seperti ditunjukkan dalam pengaturan di atas, user8647 diprogram untuk mengakses hanya tingkat 1-10. Oleh karena itu, dalam
event log, hanya relay dari 1 sampai 10 diaktifkan.
- Durasi untuk aktivasi relay juga diprogram. Secara default, itu adalah 4 detik. Ini berarti jika
tombol tidak ditekan dalam waktu 4 detik, sekarang saatnya keluar. Pengguna perlu menunjukkan kartu lagi.
Sedang diterjemahkan, harap tunggu..
 
Bahasa lainnya
Dukungan alat penerjemahan: Afrikans, Albania, Amhara, Arab, Armenia, Azerbaijan, Bahasa Indonesia, Basque, Belanda, Belarussia, Bengali, Bosnia, Bulgaria, Burma, Cebuano, Ceko, Chichewa, China, Cina Tradisional, Denmark, Deteksi bahasa, Esperanto, Estonia, Farsi, Finlandia, Frisia, Gaelig, Gaelik Skotlandia, Galisia, Georgia, Gujarati, Hausa, Hawaii, Hindi, Hmong, Ibrani, Igbo, Inggris, Islan, Italia, Jawa, Jepang, Jerman, Kannada, Katala, Kazak, Khmer, Kinyarwanda, Kirghiz, Klingon, Korea, Korsika, Kreol Haiti, Kroat, Kurdi, Laos, Latin, Latvia, Lituania, Luksemburg, Magyar, Makedonia, Malagasi, Malayalam, Malta, Maori, Marathi, Melayu, Mongol, Nepal, Norsk, Odia (Oriya), Pashto, Polandia, Portugis, Prancis, Punjabi, Rumania, Rusia, Samoa, Serb, Sesotho, Shona, Sindhi, Sinhala, Slovakia, Slovenia, Somali, Spanyol, Sunda, Swahili, Swensk, Tagalog, Tajik, Tamil, Tatar, Telugu, Thai, Turki, Turkmen, Ukraina, Urdu, Uyghur, Uzbek, Vietnam, Wales, Xhosa, Yiddi, Yoruba, Yunani, Zulu, Bahasa terjemahan.